Opal Pro to SAF GlobalData
Page 10
I/O Configuration
The Opal Pro supports 4 input words and 51 output words. Their
description is as follows:
Input
Words
Name
Description
Word 1
Command
Bit 0 Run Command
Bit 1 Jog Command
Bit 2 Reverse Command
Bit 3 Reset Command
Bit 4 DCI/Soft Stop Enable
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Watch Dog bit (this bit
must change at least twice in the
time set by parameter 15.05)
Word 2
Current
Reference
0 1000, 833 = 500% of Motor
Current set in parameter 13.01
Word 3
Phase Angle
Reference
0 (0.5 * Line Freq Cycle time in
usec)
ie: 60 Hz 0 8333
Word 4
Reserved